CHILL WATER APPLICATIONS

An ice storage system manufactures its own ice and stores it until chilled water is needed by the air conditioning equipment. An ordinary reciprocating compressor is used with whatever condensing means is appropriate for the installation. One type of evaporator, Figure 7-P (see below), consists of hollow plates submerged in a water tank. The expansion valve meters refrigerant into one end of the plates and the suction line of the compressor is connected to the other end. The heat of vaporization for the refrigerant is taken from the water surrounding the plates, causing the water to freeze on the outer surface of the plates. Controls are arranged to stop the compressor when the ice has reached the desired thickness. A float valve for controlling water level and a three-way mixing valve for temperature control can be installed in the same manner as for the ice melting system. Tanks of evaporator plates can be connected in parallel, Figure 7-Q, to obtain any desired ice storage capacity.

The ice storage system uses a small refrigeration plant to meet a high peak demand of short duration by providing storage of refrigeration. This points to the advantage of the ice storage system which is a lower initial cost than a larger system that must be designed for a high peak load without storage.

In some localities a rather high demand charge is placed on electric service. In such instances the smaller equipment means considerable savings in power cost because of a much lower demand charge. Compared with conventional refrigeration systems the ice storage system has the disadvantage lead time before occupancy. The lead time is the number of hours of compressor operation required to freeze ice to a thickness necessary to meet the peak load.

As an example of the capacity of an ice storage system, the evaporator plates in the picture below are approximately 3 ft. x 9ft. and, with ice one-inch thick, would yield approximately 7.5 tons of refrigeration per plate. Such an installation could replace a 100 ton refrigeration plant. Electric utilities look with favor upon such installations, for an ice storage system means a 15 or 20 horsepower compressor operating 10 to 12 hours in a day as contrasted to a 100 horsepower unit running for two hours.

For ice systems the cost (in dollars per ton) of secondary equipment (bunker or evaporator plates, piping, etc.) tends to decrease as the capacity of the system increases. Thus, for a small system of 20 tons the secondary equipment is a relatively large percentage of the refrigeration plant; whereas, for a 200 ton system, the secondary equipment has a lower unit cost. This act, coupled with the development of larger unitary equipment, means that an ice system could sometimes be attractive for large loads. However, considerable space is needed for ice bunkers, which may be a disadvantage. An economic study preceding the selection of an ice refrigeration system should include:

  1. Daily load in tons plotted against clock time for each zone of the building
  2. Days during the week when each area will be occupied
  3. Diversity factor between zones or areas
  4. Initial cost of equipment
  5. Electric power rate schedules
  6. Operating costs: labor, purchased ice, electric power, condensing water, and maintenance.

Back to top
© 2001 Copyright AirTec Heating & Cooling Inc.